The Amerex 10173 Vent Check is a safety device required in the actuation network of Amerex Dry Chemical / ICS / Modular systems that use nitrogen pressure. Installed downstream of the Pneumatic Control Head (or the Electric/Pneumatic Control Head), this valve helps relieve residual pressure that builds up after system activation, preventing unintended or delayed opening of the control head valve. Built of machined brass with an internal spring and nylon ball mechanism, it helps ensure reliable system reset and safe operation.
Model/SKU: 10173
Brand: Amerex
Function: Provides pressure relief in actuation piping to prevent accidental or premature valve opening due to trapped nitrogen pressure.
Compatible Components: Works with Amerex Pneumatic Control Head 10147 and Electric/Pneumatic Control Head models; part of Modular Dry Chemical or ICS system actuation networks.
Connection / Threads: 1/4″ NPT port (female) thread.
Construction: Machined brass body; includes internal spring & nylon ball; comes with dust cap (plastic) for the port when not in active service.
Why It Matters: Without a vent check, pressure can accumulate in lines that can accidentally trigger or interfere with system actuation. This part helps maintain safety, proper system reset, and reliability of suppression systems.